Load table 41×41×2.5 slotted
The full table for the most common channel. Read both columns: over short spans strength governs, over long spans deflection.
| Span (mm) | Max. load (kN) | Deflection (mm) | L/200 (kN) | L/360 (kN) |
|---|---|---|---|---|
| 250 | 16.07 | 0.3 | – | – |
| 500 | 8.03 | 1.1 | – | – |
| 750 | 5.36 | 2.4 | – | 4.74 |
| 1,000 | 4.01 | 4.2 | – | 2.66 |
| 1,250 | 3.21 | 6.5 | 3.07 | 1.71 |
| 1,500 | 2.68 | 9.4 | 2.13 | 1.18 |
| 1,750 | 2.30 | 12.8 | 1.56 | 0.86 |
| 2,000 | 2.00 | 16.7 | 1.20 | 0.66 |
| 2,250 | 1.79 | 21.2 | 0.94 | 0.52 |
| 2,500 | 1.60 | 26.2 | 0.77 | 0.42 |
| 2,750 | 1.45 | 31.6 | 0.63 | 0.34 |
| 3,000 | 1.33 | 37.7 | 0.53 | 0.29 |
Source: Atkore UK (Unistrut), Beam Loading, uniformly distributed load. Indicative.
Frequently asked questions
How much weight can a Unistrut bracket hold?
That depends on the channel and the span. A 41×41×2.5 slotted channel carries about 4 kN uniformly distributed over 1,000 mm and about 2 kN over 2,000 mm (manufacturer data, indicative). The fixings and supports also need checking.
Why is the load at L/360 lower?
Because deflection, not strength, governs. L/360 means the channel may deflect at most 1/360 of the span, for example 2.8 mm over 1,000 mm.
What is the column load?
The load an upright channel can carry before buckling, here with a fixed base. Relevant for H-frame uprights and wall channel.
Does this apply to every brand?
No. The values come from one manufacturer. Others publish their own tables; always use the table for the channel you install.